Product Details
- Voltage24 v
- MountScrew
Description
Electronic-Pneumatic Transducers are used in electronic-pneumatic
control systems to convert a proportional electric output signal from a
controller into a direct-acting, proportional pneumatic signal.
- Screw mounting or snap rail (models with cover).
- Factory calibrated.
- Dual barb fittings.
- High accuracy.
- Application: Electric to pneumatic Transducer.
- Maximum Safe Operating Pressure (psi): 30 psi.
- Output Pressure Range: 3 to 15 psi.
- Connections: Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing.
- Electrical Connections: 30 in. (762 mm) lead wire.
- Action: Direct Acting.
- Airflow Usage: 0.025 scfm (117mL/s).
- Max. Operating Temperature: 131 F.
- Input Signal: 2 to 10 Vdc at 0.1 mA max.
- Normal High End Pressure: 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc (min).
- Normal Low End Pressure: 0.5 psi at 0 Vdc.
- Pressure Range: 0 to 18 psi.
- Voltage: 24 Vac external transformer.
- Humidity Range: 5 to 95% RH.
- Comments: Without cover, external transformer required, 24 Vac, 50/60 Hz, (3 wire).