Product Details

  • Max Pressure15 PSI
  • Reset TypeAutomatic
  • Electrical Ratings (AFL)5.8 A @ 120 VAC (N.C)
  • Electrical Ratings (ALR)34.8 A @ 120 VAC (N.C)
  • SwitchSPDT
  • Voltage120 v
  • Power Consumption4.2 VA

Description

Intermittent Level Test – Maximum Protection for Foaming Boilers.
  • 15 Second Burner Off Delay
  • 30 Second Burner On Delay
  • Automatic Reset
  • Low Water Indicating Light
  • Direct Boiler Mounting – Eliminates Blowdowns Burner circuit contacts open after 15 second delay in a low water condition. Delay prevents short cycling caused by momentary fluctuations in the boiler water level. Automatically reactivates burner circuit 30 seconds after water reaches the probe, allowing optional water feeder to raise water level above the probe. Intermittent Level Test (ILT) feature provides maximum boiler protection by removing power from the burner circuit at set intervals
  • This model performs the ILT every 15 minutes for 60 seconds