Description
- Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems.
- Provide multizone control by using a separate circulator and R845 Relay for each zone.
- Include diaphragm powerhead and Micro Switch+ assembly that respond to temperature changes in boiler water.
- Mount directly to boiler.
- Select models include large transformers and extra terminals for supplying power to low voltage zone valves.
- Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus current draw of gas valve on L8124E).
Product Specifications:
Description : Triple Aquastat Relay with High limit : 10 F fixed; low limit: 10-25 F adj. DifferentialApplication: Triple Aquastat Relay with High limitOperating Range, Low Limit (F): 110 F to 220 FOperating Range, Low Limit (C): 43 C to 104 COperating Range, High Limit (F): 130 F to 240 FOperating Range, High Limit (C): 54 C to 116 CDifferential Temperature (F): High limit : 10 F fixed; low limit: 10-25 F adj.Switching Action: SPST: High & Low LimitMaximum Safe Operating Pressure (psi): 200 psi on outside of immersion well, 100 psi on capsule if inserted directly.Maximum Safe Operating Pressure (kPa) 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.Electrical Ratings (burner AFL): Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacElectrical Ratings (burner ALR): Line Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 VacElectrical Ratings (circulator AFL): 3.7 A @ 240 VacElectrical Ratings (circulator AFL): 7.4 A @ 120 VacElectrical Ratings (circulator ALR): 22.7 A @ 240 VacElectrical Ratings (circulator ALR): 44.4 A @ 120 VacVoltage: 24 VacVoltage: 120 VacFrequency: 60 HzDimensions (in.): 4 3/8 in. high x 6 1/8 in. wide x 3 1/16 in. deepDimensions (mm): 111 mm high x 156 mm wide x 78 mm deepMounting: HorizontalOperating Humidity Range (% RH): 0 to 95% RH, non-condensingMaximum Ambient Temperature (F): 150 F at switches, 265 F at sensing element.Maximum Ambient Temperature (C): 66 C at switches, 129 C at sensing element.Minimum Ambient Temperature (F): -30 FMinimum Ambient Temperature (C): -9 CElectrical Connections : Quick-Connect / ScrewL8124L1011L8124L1011/U
B008HOSUZI
0085267055055085267055055
ResideoSystem SensorGenesisHoneywell AnalyticsThermal SolutionsSalisburySelecta IncHoneywellSelectaFirst AlertBRKAubeHoward LeightAirSoft