Description
The Fireye BurnerLogix System is a microprocessor based burner
management control system designed to provide the proper burner
sequencing, ignition and flame monitoring protection on automatically
ignited oil, gas and combination fuel burners. In conjunction with limit
and operating controls, it programs the burner/blower motor, ignition
and fuel valves to provide for proper and safe burner operation. Through
smart LED's, the control provides current operating status and lockout
information in the even of a safety shutdown. Optional VFD and LCD
displays are available that may be either plugged in or mounted remotely
to give full language descriptors of current status and diagnostic
lockout information. A complete BurnerLogix system includes the YB110 (YB230) chassis
equipped with the type of flame amplifier required for the application,
appropriate flame detector, plug-in programmer module, wiring base and
optional alpha-numeric display. Interchangeable programmer modules allow
for complete versatility in selection of function, timing and flame
failure response times. The optional alpha-numeric display is made up of
2 lines by 16 characters per line and is available in either vacuum
fluorescent or liquid crystal formats. Both displays contain a fully
functional keypad allowing the user to easily scroll through the various
menus to view the current operating status, review programmer
configuration, and lockout history. An advantage of the BurnerLogix
control family is the ability to set many of the operating parameters
associated with proper and reliable burner operation allowing inventory
of various programmer types to be kept to a minimum. Interchangeable YP programmer modules allow for complete versatility in
selection of control function, timing and flame scanning means.
Functions such as pre-purge time, recycling or non-recycling interlocks,
high fire proving interlock and trial for ignition timing of the pilot
and main flame are determined by the programmer module. The BurnerLogix
system can be used with ultra-violet, auto-check infrared, flame rod,
self-check ultra-violet flame scanners or direct coupled integrated
scanners by choosing the proper chassis/flame amplifier module. Wiring bases for the BurnerLogix control are available pre-wired with 4
foot lead wires color coded and marked for easy installation or with an
integral terminal block capable of accepting up to 2 x 14 AWG wires. The
wiring base terminal block is available with knockouts for conduit or
open ended for cabinet mounting. The pigtail wiring base is 4" x 5" and
the terminal block wiring base is 4" x 7".
Functions:
- A consistent flame signal read-out via display module or 4-20 mA output.
- Read-out of main fuel operational hours and complete cycles via display module.
- Modbus communications via RS485 multi-drop link.
- Proof of fuel valve closure during off cycle.
- Burn-in time of program parameters occurs after 8 hours of main valve on time.
- A run/check switch which allows the operator to stop the program sequence in any of four different positions (Purge, PTFI, MTFI or Auto).
- Remote Display mounting with NEMA 4 protection.
- Remote Reset.
- Revert to pilot can increase burner turn down.