Product Details

  • Temperature Range100 to 250 °F
  • DifferentialHigh Limit: 25°F
  • Switch ActionFan switch makes on temp rise, High Limit switch breaks on temp rise
  • Voltage120/240 VAC

Description

For control of high limit and fan motor in all types of forced air heating systems.
  • Three wiring terminal options available for easy installation:
  • Push-in receptacles for stripped wire.
  • Female receptacles for 1/4 in. male flag connectors.
  • Field add-on screw terminals.
  • Controls adapt to many competitive mounting holes in replacement applications.
  • Available in a variety of fan and high limit setting ranges.
  • L4064B,W models have manual fan switch that overrides fan control to keep fan running continuously.
  • SUPER TRADELINE models with mounting adapters for easy installation and strain relief bushings to protect wiring from field abuse.
  • Application: Forced warm air heating systems.
  • High Limit Temperature Range (F): 100 to 250 F.
  • Fan on Range: 65 to 215 F.
  • Fan off Range: 50 to 200 F.
  • High Limit Stop: 200 F.
  • Low Limit Stop: 100 F.
  • Fan on Stop: 100 F.
  • Switching Action: Fan switch makes and high limit switch breaks on temperature rise.
  • Electrical Rating(AFL): 14 A @ 120 Vac.
  • Electrical Rating (AFL): 7 A @ 240 Vac.
  • Electrical Rating (ALR): 84 A @ 120 Vac.
  • Electrical Rating (ALR): 42 A @ 240 Vac.
  • Electrical Rating Limit (AFL): 4 A @ 240 Vac.
  • Electrical Rating Limit (AFL): 8 A @ 120 Vac.
  • Electrical Rating Limit (ALR): 24 A @ 240 Vac.
  • Electrical Rating Limit (ALR):48 A @ 120 Vac.
  • Operating Temperature Range: -40 to 190 F.
  • Differential Temperature: High limit 25 F.
  • Maximum Ambient Temperature (F): Switch: 190F; Sensing Element: 350 F.