Description
Used to control the pressure of the air delivered to pneumatic control
systems. Models available for single-pressure systems or two-pressure
systems (Day/Night or Summer/Winter) requiring two independently
regulated pressure settings. Dual-pressure units switch from the lower
settings to the higher settings when main air is applied to the pilot
port. Models also available including a sub-micron filter assembly and
pressure gauges. Replacement devices are available for Johnson, Powers,
Robertshaw, Barber-Colman and older Honeywell pressure reducing valves.
- Built-in adjustable safety relief valve for limiting downstream pressure.
- For two-pressure models: Pressure changes accomplished with manual switch or automatically with electric pneumatic switch.
- Adjustable stops for desired settings.
- Description: High Pressure Diaphragm Operated Reducing Valve with Built-in Adjustable Relief Valve for Single Pressure Systems. Includes Mounting Bracket and Gage Taps But No Gages.
- Application: Pressure Reducing.
- Output Pressure Range (psi): primary pressure: adj.0 to 25 psi.
- Connection Size: Inlet and out air: 1/4 in. NPT (female) Air gage: 1/8 in. NPT (female).
- Mounting : Bracket furnished.
- Dimensions (in): 11 in. high, 8-7/8 in. wide, 3-3/4 in. deep.
- Includes: Gage tapping to measure the regulated pressure.
- Inlet Pressure Range: 45 to 150 psi.