Immersion-type controllers that combine high limit protection with low
limit and circulator control in forced hydronic heating systems,
including domestic hot water service.
- Provide multizone control by using a separate circulator and R845 Relay for each zone.
- Include diaphragm powerhead and Micro Switch+ assembly that respond to temperature changes in boiler water.
- Mount directly to boiler.
- Select models include large transformers and extra terminals for supplying power to low voltage zone valves.
- Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus current draw of gas valve on L8124E).
- Description: Triple Aquastat Relay with High limit : 10 F fixed; low limit: 10-25 F adj. Differential.
- Application: Triple Aquastat Relay with High limit.
- Operating Range, Low Limit (F): 110 F to 220 F.
- Operating Range, Low Limit (C): 43 C to 104 C.
- Operating Range, High Limit (F): 130 F to 240 F.
- Operating Range, High Limit (C): 54 C to 116 C.
- Differential Temperature (F): High limit : 10 F fixed; low limit: 10-25 F adj.
- Switching Action: SPST: High & Low Limit.
- Maximum Safe Operating Pressure (psi): 200 psi on outside of immersion well, 100 psi on capsule if inserted directly.
- Maximum Safe Operating Pressure (kPa): 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.
- Electrical Ratings (burner AFL): Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 Vac.
- Electrical Ratings (burner ALR): Line Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac.
- Electrical Ratings (circulator AFL): 3.7 A @ 240 Vac.
- Electrical Ratings (circulator AFL): 7.4 A @ 120 Vac.
- Electrical Ratings (circulator ALR): 22.2 A @ 240 Vac.
- Electrical Ratings (circulator ALR): 22.7 A @ 240 Vac.
- Frequency : 60 Hz.
- Dimensions (mm): 156 mm high x 111 mm wide x 78 mm deep.
- Mounting : Vertical Mount Operating Humidity Range (% RH): 0 to 95% RH, non-condensing.
- Maximum Ambient Temperature (F): 150 F at switches, 265 F at sensing element.
- Maximum Ambient Temperature (C): 66 C at switches, 129 C at sensing element.
- Minimum Ambient Temperature (F): -30 F.
- Minimum Ambient Temperature (C): -9 C.
- Electrical Connections: Quick-Connect / Screw.