Product Details
- Voltage120/240 VAC
- MountSurface
- Temperature Range-35 to 150 °F
Description
- Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element.
- Models have snap-acting switching to open or close a circuit on pressure rise.
- Have adjustable differentials.
- Adjustments are made by screws on top of case.
- Mount using 1/4 inch -18 NPT internal pipe threads or surface mount through base of case.
- Ground screw terminal.
- Application: Provide control of steam, air, non-combustible gases or non-corrosive fluids.
- Mounting: 1/4 in. NPT internal thread or surface mount through back of case.
- Approvals: Underwriters Laboratories Inc. Listed: File No. MP466, Guide No. MBPR.
- Approvals: CSA Certified: File No. LR1620, Guide No. 400-E-O.
- Electrical Connections: Screw terminals.
- Contact Ratings: 120 Vac Switch Contact-- 8.0 AFL, 48.0 ALR,
10.0 A resistive; 240 Vac Switch Contact-- 5.1 AFL, 30.6 ALR, 5.0 A
resistive.
- Operating Temperature Range (F): -35 F to +150 F.
- Operating Temperature Range (C): -37 C to +66 C.
- Approvals, Swiss RE: Acceptable.
- Sensor Element: Stainless Steel diaphragm.
- Operating Range (psi): 10 to 150 psi; 225 psi - Maximum Sustained.
- Operating Range (kPa): 69 to 1034 kPa; 1151 kPa - Maximum Sustained.
- Differential Pressure Range (psi): 10 to 22 psi.
- Differential Pressure Range (kPa): 60 to 152 kPa.
- Differential Type: Subtractive.
- Switch Operation: Auto recycle.
- Switching Action: SPDT snap action, make R-W, break R-B on pressure rise.
- Pipe Connection: Main or High Pressure--1/4 in. NPT internal thread.
L404F1102L404F1102/U
B003CVRB60
0085267049993085267049993
ResideoSystem SensorGenesisHoneywell AnalyticsThermal SolutionsSalisburySelecta IncHoneywellSelectaFirst AlertBRKAubeHoward LeightAirSoftUvex