Product Details
- Voltage24 v
- Size1/2 in
- Hertz60 Hz
- Temperature Range0 to 175 °F
- Capacity (BTU)150000 BTU
- Max Pressure1/2 PSI
- Fuel TypeNatural Gas
Description
Combination gas control for use in 24 Vac, gas-fired, intermittent pilot appliances with capacities from 20 to 200 cfh.
- Controls include manual valve, two automatic operators, servo pressure regulator and pilot adjustment.
- Use with S86F,H; S8600F,H and S8610 Control Modules.
- Compact size.
- Provide two automatic valves.
- Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
- Diaphragm operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted.
- Meets codes requiring dual safety shutoff.
- Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.
- All adjustments and wiring connections are accessible from top of control.
- ON-OFF lighting sequence.
- Description:
24 Vac Dual Intermittent Pilot Gas Valve with 1/2 in. x 1/2 in.
inlet/outlet, standard opening and 3.5 in. wc pressure regulator setting.
- Type: Single Stage.
- Ignition Type: Intermittent Pilot.
- Type of Gas: Natural.
- Inlet/Outlet Size (in.): 1/2 in. x 1/2 in.
- Body Pattern: Straight-through.
- Opening Characteristics (standard, step): Standard.
- Capacity @ 1 in. p.d.: 150,000 BTU/hr; 20,000 BTU/hr minimum.
- Pressure Ratings (psi): 1/2 psi.
- Pressure Ratings (kPa): 3.5 kPa.
- Pressure Regulator Setting (psi): 3.5 in. wc.
- Pressure Regulator Setting (kPa): 0.87 kPa.
- Pilot Gas Outlet: Compression fitting for 1/4 in. OD tubing.
- Pressure Tapping: 1/8 in. NPT with plug.
- Electrical Connections: 1/4 in. quick-connect male terminals.
- Electrical Ratings: 24 Vac.
- Frequency: 60 Hz.
- Anticipator Setting: 0.5 A.
- Temperature Range (F): 0 F to 175 F.
- Temperature Range (C): -18 C to +79 C.
- Mounting: 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Dimensions (in.): 4 5/8 in. high x 4 1/8 in. wide x 2 11/16 in. deep.
- Dimensions (mm): 117 mm high x 104 mm wide x 69 mm deep.
- Includes: Natural to LP Conversion Kit, one 1/2" x 3/8" reducer bushing, one 3/4" straight flange.
- Approvals, American Gas Association IAS: AGA Design Certificate: L2025006.
- Approvals, Canadian Gas Association: CGA Design Certificate: L2025006.
- Approvals, Underwriters Laboratories Inc: UL Component Recognized: MH5323.
- Approvals, Australian Gas Association: Australian Gas Assoc. Design Certificate: 4214; Approved for Delta C Applications.
Note: This
product must be installed by a qualified/licensed contractor and set up
with properly calibrated combustion test equipment. Failure to comply
with this could result in substantial property damage, severe personal
injury or death.