Note: Heating, ventilation, air conditioning or refrigeration parts and accessories should only be installed by qualified technicians. Failure to understand and follow the manufacturer’s installation and use instructions may result in fire or explosion, electric shock, property damage, injury or loss of life. It is your responsibility to seek professional advice when installing and using these parts and accessories.
LED Flash Codes - One Flash: Lockout due to failed ignition or flame dropout; Two Flashes: Pressure Switch Fault; Three Flashes: Limit Switch is Open; Four Flashes: Undesired Flame; Five Flashes: Roll-Out Switch is Open; Continuously ON: Normal Operation.